Speed controller for induction motors, with built-in RFI filters. EMC and LVD compliant.
The inverters are suitable for High/Low Overload (constant/variable torque) applications. To control pumps and fans for heating , ventilation and air conditioning systems, normally Low Overload inverters are used. Industrial or process installations normally require High Overload inverters.
Features
•
AC choke included for protection against overvoltage
•
flexible I/O configuration; 1 free slot
•
compact housing
•
power module with metal chassis for compliance with RFI regulations and safety
•
detachable HMI-panel for parameter settings, alarms, start/stop functions, using a code-number system
•
1 all-round software package included, other packages can be installed on site
•
CE-Mark declaration enclosed in manual
Series
NXL
RFI-filter
integrated
Brake
integrated
Input phase
3
Rated voltage
380..500V (400Vnom)
Output frequency
0 ... 320 Hz
Frequency resolution
0.01 Hz
Serial communication
optional: Interbus-S, Modbus, Echelon, Profibus
Immunity
EN61800-3 (H)
Emissions
EN61800-3 (H)
Safety
EN 50178, CE, UL, C-UL, FI, GOST R
Power ratings at 380 V power supply
Protection class
High overload (for Machines)
High overload Icont
Low overload (for Fan/Pump)
Low overload Icont
Type
kW
A
kW
A
IP21
0.75
2.2
1.1
3.3
NXLAA03C2
IP21
1.1
3.3
1.5
4.3
NXLAA04C2
IP21
1.5
4.3
2.2
5.6
NXLAA05C2
IP21
2.2
5.6
3
7.6
NXLAA07C2
IP21
3
7.6
4
9
NXLAA09C2
IP21
4
9
5.5
12
NXLAA12C2
IP21
5.5
12
7.5
16
NXLAA16C2
IP21
7.5
16
11
23
NXLAA23C2
IP21
11
23
15
31
NXLAA31C2
IP21
15
31
18.5
38
NXLAA38C2
IP21
18.5
38
22
46
NXLAA46C2
IP21
22
46
30
61
NXLAA61C2
Power ratings at 380 V power supply
Protection class
High overload (for Machines)
High overload Icont
Low overload (for Fan/Pump)
Low overload Icont
Type
kW
A
kW
A
IP54
0.75
2.2
1.1
3.3
NXLAA03C5
IP54
1.1
3.3
1.5
4.3
NXLAA04C5
IP54
1.5
4.3
2.2
5.6
NXLAA05C5
IP54
2.2
5.6
3
7.6
NXLAA07C5
IP54
3
7.6
4
9
NXLAA09C5
IP54
4
9
5.5
12
NXLAA12C5
IP54
5.5
12
7.5
16
NXLAA16C5
IP54
7.5
16
11
23
NXLAA23C5
IP54
11
23
15
31
NXLAA31C5
IP54
15
31
18.5
38
NXLAA38C5
IP54
18.5
38
22
46
NXLAA45C5
IP54
22
46
30
61
NXLAA61C5
Description
Additional Product Type
Filter for frame sizes MF2 or MF3
ACC/NXL/FILTER/FR2-3
Kit to mount NXL frame size MF2 on DIN rail
ACC/NXL/MF2DIN
NXL to PC cable (also requires use of RS232 adaptor below)
ACC/NXL/RS232PC
I/O expander card with 3x Digital Input, 1x Digital Output (open collector) and 1x Relay Output (changeover). Fitted as standard to the Ecodrives and available as an optional extra for the Microdrives
NXOPTAA
NXL RS232 adaptor for use with NXL to PC cable
ACC/RS232/ADAPTOR
Door mounting kit for control keypad
NXLDRA
Copyright 2007-2008 Sunlinx Control Systems Limited, All Rights Reserved
Tel:+8610 68723890 Fax:+8610 68725160
Address: No:35 Che Gong Zhuang West Road Beijing,China Postcode:100044
China High-Tech Enterprise Registered Code:0611002B01395